美国进口
Imported from USA

清除沉淀空气分离器
Sediment Removal Separator


美国贝尔-高赛特
Bell & Gossett

The Bell & Gossett Sediment Removal Separator (SRS) is a patented centrifugal style air and sediment separator for use in any HVAC system. Its 3-to-1 body diameter to nozzle diameter ratio slows the fluid velocity to allow entrained air and suspended sediment to come out of solution, while its tangential inlet and outlet nozzles induces centrifugal fluid flow. This centrifugal flow creates a low pressure vortex in the center of the tank where entrained air can come out of solution and float to the top of the tank and suspended sediment can sink to the bottom. In addition, the SRS features an extended collection cap at the bottom of the tank where sediment can collect without the risk of being pulled back into the system by the exiting fluid. These impurities can then be easily removed via an air vent or connection to an expansion tank and a blowdown valve.

Contaminants such as air and suspended sediment can lead to diminished heat transfer, higher energy costs, damage to your system components, and increased system noise. By removing them you can lower the cost to operate your system, extend the life of your components, and provide better comfort to your building occupants.

All SRS models are designed, constructed, inspected, and stamped per Section VIII, Division 1 of the ASME code for 125 psi (862 kPa) maximum working pressure and 350°F (177°C) maximum working temperature. Higher pressures and temperatures are available upon request. Models are available in sizes 3″ through 36″ and are available with NPT (3″ only), flange, or groove end connections.

Features and Benefits

Removes Entrained Air and Suspended Sediment

  • To protect the system against damage
  • To provide better heat transfer
  • To reduce energy costs
  • To eliminate system noise

Centifugal Flow Pattern

  • Creates low pressure vortex in center of tank
  • Lowers pressure drop through the tank

Models from 3″ – 36″

    • Carbon steel body

-Other body materials available upon request for 3" – 36" models)

  • NPT (3″ only), flange, or groove connections available
  • Includes extended collection cap on bottom of tank to prevent sediment from being pulled back into the system

Designed, constructed, inspected, and stamped per Section VIII, Division 1 of the ASME Code

  • Standard models rated for 125 psi (862 kPa) working pressure. Higher pressures available upon request

Models – Part Number (see Brochure A-514C for dimensions & weights)

Flanged Grooved
3 or 3G – 5366-03C-12-001 3 or 3G – 5366-03G-12-001
4 or 4G – 5366-04F-12-001 4 or 4G – 5366-04G-12-001
5 or 5G – 5366-05F-12-001 5 or 5G – 5366-05G-12-001
6 or 6G – 5366-06F-12-001 6 or 6G – 5366-06G-12-001
8 or 8G – 5366-08F-12-001 8 or 8G – 5366-08G-12-001
10 or 10G – 5366-10F-12-001 10 or 10G – 5366-10G-12-001
12 or 12G – 5366-12F-12-001 12 or 12G – 5366-12G-12-001

Bell & Gossett offers several useful engineering tools for easy sizing of every area of a building. Simple to navigate software gives you accurate information and up-to-date documentation downloadable straight into your submittal package.

Some tools require a registered account: New User Registration | Existing User Password Help

ESP-Design Plus Bell & Gossett: Multi-Stage, Pressure Booster Packages, Wastewater, Vertical Turbines
ESP-Plus Bell & Gossett Pump Selection: Circulators, End Suction, Closed-Coupled, Inline, Double Suction
ESP-Tanks Bell & Gossett Compression/Expansion Tanks and Accessories (downloadable app)
ESP-Thermal Bell & Gossett Gasket Plate & Frame and, Brazed Plate Heat Exchangers
ESP-UTUBE Bell & Gossett U-Tube Heat Exchangers
ESP-Parts Parts Selection
Steam-2000 Steam 2000 Selection
Steam-1140 Series 1140 Steam Service Regulators
Water-1140 Series 1140 Water Service Regulators
Steam-Traps Steam Traps Selection
CAD Drawings CAD Drawings
System Syzer System Syzer (available online, PC download, and iOS app)
System Syzer Psychrometry System Sizing related to coil cooling (link downloads .exe file)
Steam-Pipe Steam Pipe Sizing
Steam-Loss Steam Loss Through Failed Trap
Flash-Steam Flash Steam Sizing
Condensate-Pipe Condensate Pipe Sizing
Mobile Catalog iOS iPhone & iPad Mobile Product Catalog
Mobile Catalog Android Android Device Mobile Product Catalog