福建省厦门市建设大厦2509单元 邮编:361001 电话:592-2121956 传真:592-2122287 E-mail: 666@h6688.com 微信:18906039241
Room 2509, Construction Building, Xiamen, Fujian 361001, China Tel: (86-592) 212-1956 Fax: (86-592)212-2287 E-mail: 666@h6688.com
美国进口 Imported from USA |
霍夫曼专业热阀芯疏水阀BearTrap |
美国贝尔-高赛特 Bell & Gossett |
Thermodisc Steam Traps
Thermodisc steam traps use flash steam velocity and pressure to move a free-floating disk to open and close a valve. Because the disc is the only moving part, the traps are rugged and resistant to damage.
This type of trap provides dependable performance for applications with light to moderate condensate loads. Thermodisc traps are excellent for high-pressure drip and steam tracing applications.
Operation of Thermodisc Traps:
At start-up, the disc is pushed off the seat by the inlet pressure and is held open by the impact force of the condensate hitting the disc.
As the condensate nears saturation temperature, flash steam will enter the seat-disc chamber at high velocity, lowering the pressure on the bottom of the disk. Some of the flash steam escapes to the area above the disc, causing the pressure above the disc to increase, pushing the disc closer to the seat.
At the instant the disc snaps closed on the seat, the pressure above the disc is approximately equal to the upstream line pressure. The disc is held closed because the pressurized area above the disc is much larger than the inlet area. The pressure above the disc decreases either by steam condensation or by non-condensables being removed via the micro-bleed channel on the disc.
When the pressure is low enough, the disc is pushed off the seat and the process is repeated.
Characteristics of Thermodisc Traps:
Primary Applications of Thermodisc Traps:
Features and Benefits
Parts Lists
Catalog Pages
Submittals
Bell & Gossett offers several useful engineering tools for easy sizing of every area of a building. Simple to navigate software gives you accurate information and up-to-date documentation downloadable straight into your submittal package.
Some tools require a registered account: New User Registration | Existing User Password Help
ESP-Design Plus | Bell & Gossett: Multi-Stage, Pressure Booster Packages, Wastewater, Vertical Turbines |
ESP-Plus | Bell & Gossett Pump Selection: Circulators, End Suction, Closed-Coupled, Inline, Double Suction |
ESP-Tanks | Bell & Gossett Compression/Expansion Tanks and Accessories (downloadable app) |
ESP-Thermal | Bell & Gossett Gasket Plate & Frame and, Brazed Plate Heat Exchangers |
ESP-UTUBE | Bell & Gossett U-Tube Heat Exchangers |
ESP-Parts | Parts Selection |
Steam-2000 | Steam 2000 Selection |
Steam-1140 | Series 1140 Steam Service Regulators |
Water-1140 | Series 1140 Water Service Regulators |
Steam-Traps | Steam Traps Selection |
CAD Drawings | CAD Drawings |
System Syzer | System Syzer (available online, PC download, and iOS app) |
System Syzer Psychrometry | System Sizing related to coil cooling (link downloads .exe file) |
Steam-Pipe | Steam Pipe Sizing |
Steam-Loss | Steam Loss Through Failed Trap |
Flash-Steam | Flash Steam Sizing |
Condensate-Pipe | Condensate Pipe Sizing |
Mobile Catalog iOS | iPhone & iPad Mobile Product Catalog |
Mobile Catalog Android | Android Device Mobile Product Catalog |